6 kW Natural Gas or LP Specifications

  • Powerful, air-cooled overhead valve engine fueled by natural gas or LP
  • Remote-mounted automatic transfer switch for fast and efficient unattended transfer to generator when utility current fails
  • Sound-dampening, weather-protective enclosure reduces exterior noise levels and includes key locks for security
  • Built-in charger keeps battery at optimum level
  • Automatic safety shutdowns protects engine and generator in event of low oil pressure, high coolant temperature and overcrank
  • 14-day excerciser automatically runs the system for 7 minutes bi-weekly to maintain top running condition
GENERATOR SET
Model EPS-6-AC
Rated Power (kW)* 6
60 Hz Phase Single
Voltage 120/240V
Amps 50.0/25.0
Engine / Alternator RPM 3600
Engine 410cc
OHVI single cyl.
Fuel Natural gas or LP
Engine Cooling Air
Dimensions (L" x W" x H") 40 x 22 x 23
Shipping Wt. (lbs.) 357
*Natural gas and LP ratings may decrease depending on btu content of local gas supply. Proper sizing of tank/piping is required to ensure full output.
TRANSFER SWITCH
No. of Poles 2
Current Rating (amps) 100
Voltage Rating (VAC) 250
Utility Voltage Monitor (fixed)
    Pick-up
    Drop out

80%
60%
Return to Utility 1 minute
Exerciser 7 min. bi-weekly Standard
UL Approved Standard
Dimensions (H" x W" x D")
    Non-UL Approved
    UL Approved

--
20 x 15 x 7
CONTROLS
Start/Stop Control Cyclic cranking: 7 seconds on, 7 seconds rest. 90 seconds overcrank protection.
Automatic Low Oil Shutdown Standard
Overspeed Shutdown Standard, 70 Hz
Overcrank Protection Standard
Automatic Voltage Regulator
with Over-Voltage Protection
Standard
Engine Warmup 15 seconds
Engine Cool-Down 1 minute
Safety Fuse Standard
Starter Lockout Starter cannot re-engage until
5 seconds after the engine has stopped
2 Amp Timed Trickle Battery Charger Standard
Mode Switch
    * Auto Switch

    * Off Switch


    * Manual/Test


Utility failure/14 day exercise

Stops unit. Power is removed.
Control and charger still operate

Start with starter control,
unit stays on. If utility fails,
transfer to load takes place

Posted generator specifications are subject to change.

 

 