- Quiet, powerful, liquid-cooled engine fueled by natural
gas or LP.
- A standard weather protective enclosure protects generator
from harmful weather and also reduces exterior noise levels.
Includes key locks for security.
- Built-in charger maintains battery at optimum performance
level.
- Automatic safety shutdowns protect engine and generator in
event of low oil pressure, high temperature, overspeed
and/or overcrank.
- Automatic seven day exerciser runs the system for fifteen
minutes each week to maintain top running condition.
- Standard 100-amp remote-mounted automatic transfer switch
for fast and efficient unattended transfer to generator when
utility source fails.
| GENERATOR SET |
| Model |
04188/04189 |
04370/04371 |
| Rated Power
(kW)* |
15 |
20 |
| 60 Hz Phase |
Single |
Single |
| Voltage |
120/240V |
120/240V |
| Amps @ 120/240V,
Single Phase 60 Hz |
125/62.5 |
166.6/83.3 |
| Engine /
Alternator RPM |
1800 |
3600 |
| Engine |
1.5L
OHC 4 cyl. |
1.5L
OHC 4 cyl. |
| Fuel |
Natural
gas or LP |
Natural
gas or LP |
| Engine Cooling |
Liquid |
Liquid |
| Dimensions
(L" x W" x H") |
49.25
x 25.75 x 33.25 |
49.25
x 25.75 x 33.25 |
| Shipping Wt.
(lbs.) |
800 |
812 |
| *
Natural gas and LP gas rating may decrease depending on
btu content of local gas supply. Proper sizing of
tank/piping is required to ensure full output. |
| CONTROLS |
| Start/Stop
Control |
Cyclic
cranking: 7 seconds on, 7 seconds rest. 90 seconds
overcrank protection. |
| Automatic Low
Oil Shutdown |
Standard |
| Overspeed
Shutdown |
Standard,
70 Hz |
| Overcrank
Protection |
Standard |
| Automatic
Voltage Regulator with Over-Voltage Protection |
Standard |
| Engine Warmup |
15
seconds |
| Engine Cool-Down |
1
minute |
| Safety Fuse |
Standard |
| Starter Lockout |
Starter
cannot re-engage until 5 seconds after engine has
stopped |
| 2 Amp Timed
Trickle Battery Charger |
Standard |
Mode
Switch
* Auto Switch
* Off Switch
* Manual / Test
|
Utility failure/7 day exercise
Stops unit. Power is removed.
Control and charger still operate
Start with starter control,
unit stays on. If utility fails,
transfer to load takes place
|
Posted generator